Cores x cross-section | External diameter | Insulation thickness | Sheath thickness | Conductor resistance at 20 °C | Short circuit current 1s | Cu weight | Cable weight |
min – max. | nom. | nom. | max. | nom. | prib. | ||
N x mm² | mm | mm | mm | Ω/km | kA | kg/km | kg/km |
1 x 50 | 14 – 17 | 1.40 | 1.80 | 0.64 | 3.80 | – | 298.00 |
1 x 70 | 16 – 19 | 1.40 | 1.80 | 0.44 | 5.32 | – | 383.00 |
1 x 95 | 18 – 21 | 1.60 | 1.80 | 0.32 | 7.00 | – | 490.00 |
1 x 120 | 19 – 22 | 1.60 | 1.80 | 0.25 | 9.12 | – | 575.00 |
1 x 150 | 21 – 25 | 1.80 | 1.80 | 021 | 11.40 | – | 695.00 |
1 x 185 | 23 – 27 | 2.00 | 1.80 | 0.16 | 14.10 | – | 845.00 |
1 x 240 | 26 – 30 | 2.20 | 1.80 | 0.13 | 18.20 | – | 1100.00 |
1 x 300 | 28 – 32 | 2.40 | 1.90 | 0.10 | 22.80 | – | 1379.00 |
1 x 400 | 32 – 37 | 2.60 | 2.00 | 0.08 | 27.20 | – | 1615.00 |
1 x 500 | 35 – 40 | 2.80 | 2.10 | 0.06 | 34.00 | – | 2015.00 |
1 x 630 | 41 – 45 | 2.80 | 2.20 | 0.05 | 42.84 | – | 2472.00 |
4 x 16 | 21 – 25 | 1.00 | 1.80 | 1.91 | 1.21 | – | 750.00 |
4 x 25 | 25 – 32 | 1.20 | 1.80 | 1.20 | 1.90 | – | 950.00 |
4 x 35 | 27 – 34 | 1.20 | 1.80 | 0.87 | 2.66 | – | 1141.00 |
4 x 50 | 29 – 36 | 1.40 | 1.90 | 064 | 3.80 | – | 1242.00 |
4 x 70 | 33 – 40 | 1.40 | 2.10 | 0.44 | 5.32 | – | 1631.00 |
4 x 95 | 38 – 45 | 1.60 | 2.20 | 0.32 | 7.22 | – | 2063.00 |
4 x 120 | 41 – 49 | 1.60 | 2.40 | 0.25 | 9.12 | – | 2538.00 |
4 x 150 | 46 – 54 | 1.80 | 2.50 | 0.21 | 11.40 | – | 3090.00 |
4 x 185 | 51 – 59 | 2.00 | 2.70 | 0.17 | 14.10 | – | 3838.00 |
4 x 240 | 57 – 65 | 2.20 | 2.90 | 0.13 | 18.20 | – | 4863.00 |
4 x 16+2.5 | 21.60 | 1.00 | 1.80 | 1.91 | 1.21 | 24.00 | 781.00 |
4 x 25+2.5 | 28.00 | 1.20 | 1.80 | 1.20 | 1.90 | 24.00 | 981.00 |
4 x 35+2.5 | 31.00 | 1.20 | 1.80 | 0.87 | 2.66 | 24.00 | 1172.00 |
4 x 50+2.5 | 35.00 | 1.40 | 1.90 | 0.64 | 3.80 | 24.00 | 1273.00 |
4 x 70+2.5 | 38.00 | 1.40 | 2.10 | 0.44 | 5.32 | 24.00 | 1662.00 |
4 x 95+2.5 | 42.00 | 1.60 | 2.20 | 0.32 | 7.22 | 24.00 | 2094.00 |
4 x 120+2.5 | 46.00 | 1.60 | 2.40 | 0.25 | 9.12 | 24.00 | 2569.00 |
4 x 150+2.5 | 49.00 | 1.80 | 2.50 | 0.21 | 11.40 | 24.00 | 3121.00 |
4 x 185+2.5 | 54.00 | 2.00 | 2.70 | 0.16 | 14.10 | 24.00 | 3869.00 |
4 x 240+2.5 | 59.00 | 2.20 | 2.90 | 0.13 | 18.20 | 24.00 | 4894.00 |
The cable is suitable for use in rated AC voltage (U0/U) 0.6/1kV system transmitting and distributing circuit. With the metal armored layer, it is suitable for mains, sub main and sub circuits unenclosed, in conduit, buried direct or in underground ducts for buildings and industrial plants where mechanical damage may occur.Used in electric power plants, transformer stations, industrial plants, metropolitan networks and in other electric plants, same as for connection of signaling devices in industry, traffic and similar.
Please fill out the form below and we will contact you as soon as possible.
We can design and manufacture various cables according to your requirement of special cable construction and special occasion and usage.